1、TKQ2 双电源自动切换开关Series Dual Power Automatic Transfer SwitchesTKQ2 Series Dual Power Automatic Transfer Switches Using OccasionTKQ2 Series Intellectual dual power automatic transfer switches (A.T.S for short) is one of the newest scientific technology products. It is used in 50Hz, 400V AC power supplyi
2、ng system, with the function of automatic transfer between the normal power supply (N) and the reserved one (R), guarantee the reliability and safety of supplying power. This product is produced according to the standard of GB/T14048.00-2002、IEC60947-6-1 Automatic Transfer Switch Electricand Water-p
3、roof Norms of Tall Residential Building, Fire-proof Norms of Building Design , Urgent Lighting Design Enchiridion, Electric Design Norms of Residential Buildingetc. It can be used widely in the places where the power cut is not allowed, such as hospital, shopping malls, bank, chemical plant, tall bu
4、ilding, military device, fire protection etc. CharacterTKQ2 series A.T.S is different from the previous transfer switches, such as the power-load switch which combined with load-switches, transfer switches which combined with contactors. TKQ2 series A.T.S is made of two new-generation molded case ci
5、rcuit breakers (MCCB), which have high breaking capacity, with its own accessories; the single electricity machinery drive with mechanical interlock and intellectual controller. It has the capacity of short circuit and over-load protection; over-voltage, under-voltage, lack of phase automatic transf
6、er function, to guarantee the electricity distribution series operating reliably. It has the following characters:1. There is a double-protection between the two circuit breakers. One is reliable mechanical interlocking mechanism; the other is the intellectual electric interlocking which core is MOT
7、OROLA Single Chip Micyoco (SCM). 2. Over-load, under-load, lacking phase automatic transfer and intellectual alarm function.3. Electricity machinery operating protection 4. The parameter can be set freely at the outside.5. Small volume, easy to fit and use. 6. Energy saving, no noise running.7. The
8、switch has electric fire fighting controller. When the fire fighting center give a control signal to the auto controller, the two circuit breakers will come to the open state. 8. It has the computer interface, so it has the function of remote control, remote regulation, remote communicate and remote
9、 transport. Working Condition1. Ambient air temperature:1) Upper limit: +402) Lower limit: -10The average temperature in 24 hours is not exceed +35.2. Altitude: the altitude of install place is not exceed 2000m3. Atmosphere condition: the relative humidity of the atmosphere is not exceed 50% when th
10、e ambient temperature is +40, and the lower temperature is, the higher humidity will be. When the lowest average temperature is 25 in the moistest month, the highest average humidity of this month is 90%, and the dew on the switch surface is also considered for the temperature changed. . Model and S
11、ignificationTK Q 2 / P 3: three poles 4: four poles rated current of circuit breaker grade frame current of circuit breaker R: self-input and self-recover S: self-input without self-recover F: utility-generator B: combined design sequence number dual power Automatic Transfer Switches enterprise code
12、 SpecificationThe main specifications are listed in sheet 1, and the special types can be communicated. Sheet 1ModelCircuitBreakerFrameCurrent (A)RatedCurrent(A)RatedVoltage (V)Rated insulatedVoltage (V)RatedFrequencypolesTKQ2-100CM1-10010010,16,20,25,32,40,50,63,80,100AC 400V690V50Hz3/4TKQ2-225CM1-
13、225225100,125,140,160,180,200,225TKQ2-400CM1-400400225,250,315,350,400TKQ2-630CM1-630630400,500,630TKQ2-800CM1-800800630,700,800TKQ2-1250CM1-12501250800,1000,1250 Main technology parameter1. Rated working voltage of intellectual controller: AC 230V2. The life time of the switch (N-R-N circulation) a
14、nd character parameter are listed as sheet 2. Sheet 2ModelTKQ2-100225TKQ2-400TKQ2-630800TKQ2-1250Electrical life (times)10001000500500Mechanical life (times)5000300025001500Working life (total)6000400030002000Rated working wayUninterrupted working wayOver-voltage transfer setting value110%Ue (cant b
15、e regulated, it was set when produced)Under-voltage transfer setting range6085% regulated continuouslyTransfer time2sOpen delay time t10.5s60sClose delay time t20.560s. Externality and Installation dimensionThe picture1 and picture2 are the externality, picture3 is the divided controller panel, and
16、the installation dimension is list in sheet3. The externality of holistic controller and installation dimension (picture1 and sheet3).Picture1 The externality of divided controller and installation dimension (picture2 and sheet3).Picture2The dimension of divided controller (picture3)Picture3Sheet3Mo
17、delABCDH1H2Three polesFour polesThree polesFour polesTKQ2-100490490460460200220195258.5TKQ2-225490490460460220240210258.5TKQ2-4006607106306802953152302510.5TKQ2-6306607106306802953152402510.5TKQ2-8006607106306802953152502510.5TKQ2-12508008007707703754003003010.5 Main structure and the working princi
18、pleTKQ3 series dual power automatic transfer switch is made of two molded case circuit breakers (MCCB), transporting structure electricity machinery with mechanical interlocks, intellectual controller etc, all the devices are installed on one panel. And the controller interior is intellectual auto c
19、ontrolling circuit, made of MOTOROLA single chip micyoco (SCM) and advanced, reliable electronic component. 1. Working principle of auto controller The auto controller tests the three phases voltage of normal and reserved power supply in the same time, when the numerical is 110% higher than the rate
20、d one, the controller views it as over-voltage, 6085% lower than the rated one is under-voltage (the user can set the specific parameter freely). The internal circuit judges the test result of the timely phase for six voltages margin. When the result passes the relay, it drives the related relay giv
21、e the open and close orders to the electricity machinery operating structure. And the above test result will be showed by some LEDs on the panel. There are four working ways (“automatic and manual”, “normal power supply”, reserved power supply”, “release ”), transfer delay time and the under-voltage
22、 numerical can be set through six push button switches. The switches are installed on the panel. 2. Test and control function of auto controller 2.1 self-input and self-recover auto controllerTKQ2 is used for the auto transforming between the normal power supply and reserved power supply. In usual t
23、ime, the power was supplied by the normal power supply, and when it become abnormal (any single phase is over-voltage, under-voltage, interrupted phase), the reserved power supply will work after the appropriate delay; when the normal power supply refined, it will work once again automatically.Make
24、sure the reserved power supply is no damaged. When it has some abnormal situation, the related LED on the panel will turn yellow, and the internal buzzer will offer an alarming signal to tell the user to restore.The function of the self-input and self-recover auto controller (sheet 4)sheet 4normal p
25、ower supplyreserved power supplycontrol functionnormalnormalnolmal power supply work; QN close, QR opennormalabnormalnolmal power supply offer an alarming signal;QN close, QR opennormalnormalQN open after delay t1, and after delay t2, QR close; reserved power supply workrecovernormalQR open after de
26、lay t1, and then QN close after delay t2normal power supply rework automatically2.2 自投不自复式auto controllerTKQ2 is used for the auto transforming between the normal power supply and reserved power supply. In usual time, the power was supplied by the normal power supply, and when it become abnormal (an
27、y single phase is over-voltage, under-voltage, interrupted phase), the reserved power supply will work after the appropriate delay; when the normal power supply refined, it cant work once again automatically, unless the reserved power supply has some problem. The situation is also fit for the contra
28、ry condition. Make sure the reserved power supply is no damaged. When it has some abnormal situation, the related LED on the panel will turn yellow, and the internal buzzer will offer an alarming signal to tell the user to restore.The function of the 自投不自复式 auto controller (sheet 5)sheet 5normal pow
29、er supplyreserved power supplycontrol functionnormalnormalnolmal power supply work; QN close, QR opennormalabnormalnolmal power supply work, reserved power supply offer alarm; QN close, QR openabnormalnormalQN open after delay t1, and after delay t2, QR close; reserved power supply workrecovernormal
30、Reserved power supply work, not recover automatically,QN open, QR closenormalabnormalQR open after delay t1, and then QN close after delay t2normal power supply work2.3 power grid generating auto controller TKQ2 is used for the auto transforming between the normal power supply and reserved power supply. In usual time, the power was supplied by the normal power supply, and when it becomes abnormal (any single phase is over-voltage, under-voltage, interrupted phase), the intellectual controller orders to release the electricity by offering a controlling request as well as a unloading order (